Retrotec DU200 DucTester Testing Procedures to meet EnergyS Uživatelský manuál Strana 3

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 4
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 2
Page 3 of 4
4.3 Envelope leakage test to meet ENERGY STAR standards
1. Remove Grill Mask and DucTester.
2. Connect the Door Fan to blow outdoors.
3. On the DM-2:
a. Press [Mode] until “Air Chg
appears.
If unavailable, see Page 4.
b. Press [Device] to get “Retrotec 1000”.
c. Press [Range Config] to get "B".
4. Press [Enter Volume], enter volume in
cubic feet, then press [Enter] to lock in
the volume for each house.
5. Press [Set Pressure] [50] [Enter].
6. Press the [@] key until “@50 Pa” is
displayed.
7. Record the envelope leakage in air
changes at 50 Pa.
Total building
leakage under
depressurization is
the most common
test direction for
residential testing.
Connect green
tube on some
models.
Zobrazit stránku 2
1 2 3 4

Komentáře k této Příručce

Žádné komentáře