Strany 2 - What you will learn

 Use a wind dampening kit

Strany 3 - What is Pressure?

Imbalanced test fan flow – Solution : common set point 1. What is the total leakage area (EqLA)? (Pick the closest answer) 10 in2 __ , 20 in2 _

Strany 4

Uneven building test pressures between floors caused by common set point Click to play video Developed by Retrotec Inc. Exercise 3

Strany 5 - There are two

Uneven building test pressures between floors caused by common set point Developed by Retrotec Inc. Exercise 3 Only 1 gauge controls the speed o

Strany 6

Uneven building test pressures between floors caused by common set point 1. What is the pressure of the right Simulator Tent? (Pick the closest answ

Strany 7 - Bias due to wind and stack

Uneven building test pressures between floors – Solution: individual set points Click to play video Developed by Retrotec Inc. Exercise 4

Strany 8 - ◦ Stabilizes readings

Uneven building test pressures between floors – Solution: individual set points Developed by Retrotec Inc. Exercise 4

Strany 9 - Testing in windy weather

Uneven building test pressures between floors – Solution: individual set points 1. What is the flow through the left Simulator Tent? (Pick the cl

Strany 10 - Use a wind dampening kit

Uneven building test pressures between floors – Solution: individual set point with manual control Click to play video Developed by Retrotec In

Strany 11 - What does taking a baseline

Uneven building test pressures between floors – Solution: individual set point with manual control Developed by Retrotec Inc. Exercise 5

Strany 12 - 3.Wait until

Uneven building test pressures between floors –Solution: individual set point with manual control 1. What is the flow through the left Simulator Te

Strany 13 - The measured baseline

Take a baseline to negate the effects of bias pressure and wind fluctuations.  What does taking a baseline do?

Strany 14

1. Press [Baseline] once. 2. Press [Start] once 3.Wait until number is steady then press [ENTER] once to save. The measure baseline is automatically

Strany 15

1. Press [Baseline] once 2. Press [Enter] after about 60 seconds. The measured baseline is subtracted from the pressure reading on Channel PrA.

Strany 16 - Avoid Problems

Learn when and how the baseline is cleared from each gauge. Leaving the baseline on, or forgetting that it’s off can cause errors during testing.  C

Strany 17 - Gauge field check

Residential Pressure Measurement Pressure gauge Troubleshooting

Strany 18

Avoid Problems

Strany 19 - Cross Port Check

 Insert a T in the tube and connect it to one reference port. Connect the other reference port as shown.  Increase the fan speed and compare Channel

Strany 20 - To outside

Learn to perform a calibration check on a digital gauge. It’s a quick and simple way to verify that the gauge is working correctly.

Strany 21

Cross Port Check 1 2 3 35.2 Pa 35.6 Pa -35.2 Pa -35.6 Pa 35.2 Pa 35.6 Pa

Strany 22 - (2X) the time

 What is pressure?  The importance of pressure in houses  Get to know your pressure gauge  Using a digital pressure gauge  Pressure gauge tests o

Strany 23 - Pinched tubes

 A moving tube can generate pressure in the tube. ◦ Do not allow tubes to hang in the path of moving air. Move tubes around and notice the effect 8.0

Strany 25 - What can cause problems

Always wait twice (2X) the time averaging period before taking a reading. Time averaging can lead to false results if the time averaging period is not

Strany 26 - Range, or

 Pinching or squishing a tube causes the measured pressure to increase Pinched tubes

Strany 27 - Some common problems are

 Water trapped in tube compresses air in the tube, even with auto-zero turned ‘ON’.  Shake out the water to clear the pressure.  A single water dr

Strany 28 - Introduction

 What can cause problems with measurements?

Strany 29

 Selecting the wrong Flow Range, or wrong device can lead to incorrect results. ◦ What happens?

Strany 30 - Flex duct

 Some common problems are frequently seen when taking multi-point tests.

Strany 31 - 12’ Flex-duct

Introduction Residential Duct Leakage Measurement rev-2011-02-21

Strany 32 -  Sample roll of 8” DuctMask

Image Courtesy of The Energy Conservatory Image Courtesy of Retrotec Inc

Strany 33

Residential Pressure Measurement What is Pressure?

Strany 34 - Pressurization test

Calibrated Fan Flex duct Flex duct flange Flex duct Image Courtesy of Retrotec Inc Image Courtesy of The Energy Conservatory

Strany 35 - Prepare ducts and house

A DucTester system includes:  DU-220 Fan with 3 flow rings + case  12’ Flex-duct  DM-2A Digital Manometer + bag  Static pressure probe  20’ umbil

Strany 36 - Duct testing guides

Duct Blaster includes:  Duct Blaster fan with 3 flow rings + case  DG-700 Digital Pressure and Flow Gauge  12’ flex duct  Duct Blaster Training vi

Strany 37 - Step 1: Connect to ducts

Open Ring 1 (A1) Ring 2 (B2) Ring 3 (C3 on gauge) 600-1000 cfm 225-800 cfm 90-300 cfm 10-125 cfm Low Mid Open 5-25 cfm 25-125 cfm 100-600 cfm Minn

Strany 38

5 step, Total duct Pressurization test Residential Duct Leakage Measurement

Strany 39

1. Connect to ducts 2. Prepare ducts and house 3. Connect gauge & fan (pressurization) 4. Measuring 5. No results displayed 5 step, Total duct Pre

Strany 40

Duct testing guides

Strany 41

Step 1: Connect to ducts Image Courtesy of Retrotec Inc Image Courtesy of Retrotec Inc Image Courtesy of The Energy Conservatory Image Courtesy of The

Strany 43

Images Courtesy of The Energy Conservatory

Strany 44

What is Pressure?

Strany 45

Step 2: Prepare ducts and house Image Courtesy of Retrotec Inc

Strany 49

25 Pa 90 cfm

Strany 50 - Turn the gauge On

Image Courtesy of Retrotec Inc

Strany 52

Fan Pressure Tap Electrical Connection Image Courtesy of The Energy Conservatory

Strany 55

There are two types of pressure that can be measure on a digital gauge.

Strany 56 - Troubleshooting

Turn the gauge On Press: x3 x3 x2 ON/ OFF Press: Press: x2 After being set up once, the gauge will return to the previous settings.

Strany 57 -  Both channels

Manually adjust fan speed Image Courtesy of Retrotec Inc Image Courtesy of The Energy Conservatory

Strany 58

Open Mid

Strany 60

Open Ring 1 (A1) Ring 2 (B2) Ring 3 (C3) 600-1000 CFM 225-800 CFM 90-300 CFM 10-125 CFM Open Mid Low 100-600 CFM 25-125 CFM 5-25 CFM Minneapolis Duct

Strany 61

Image courtesy of Retrotec Inc Image courtesy of The Energy Conservatory Image Courtesy of Retrotec Inc -25 Pa 90 cfm

Strany 62 -  Duct leakage to outdoors

• Not able to reach target pressure • Check covers on all registers • Tape may be being blown off during pressurization • Duct system just too leaky t

Strany 63 - Pressurization to outdoors

 Connect the red and yellow ports.  Both channels should have same reading within 1%.

Strany 64 -  The leaks measured

Image Courtesy of Retrotec Inc

Strany 65 - 100 cfm

Pressurization leakage to outdoors Residential Duct Leakage Measurement

Strany 66 - Leak location

 Stack effects & Wind effects Measure indoor/outdoor bias pressures caused by: -1.0Pa To outside

Strany 67 - Duct Simulator setup

Image Courtesy of Retrotec Inc

Strany 69 - Guiness World Record

After completing the total duct leakage test, a duct leakage to the outdoors test can be completed by adding a door fan to the test setup.  Duct leak

Strany 70

Pressurization to outdoors Image Courtesy of Retrotec Inc 25 Pa 25 Pa 25 Pa 0 Pa 40 cfm 40 cfm

Strany 71

 Duct leakage to outdoors test  The duct leakage to the outdoors test neutralizes air leakage between the duct and interior of the house, by maintai

Strany 72

Pressurization to outdoors – Single gauge 25Pa 100 cfm Image Courtesy of Retrotec Inc 25 Pa 40 cfm 25 Pa 40 cfm

Strany 73 - Acceptable air leakage?

Leak location Residential Duct Leakage Measurement

Strany 74 - Real life test: EMAD

Duct Simulator setup  Setup the duct simulator with leakage to the house and to the outdoors (with the house simulator tent).  Build your own simula

Strany 75 - Real life test: BTC

Large Building Testing Developed by Retrotec Inc.

Strany 76 - Real life test: Retrotec

Guiness World Record 15,000,000 cubic feet

Strany 77 - Face page and graphs for MFT

Bias due to wind and stack Bias pressures under windy conditions

Strany 79

Year of Construction Year of Air-barrier retrofit? Number of Stories Floor Area Enclosure Area Tested Permeablity ft2 ft2 cfm/ft2 @75Pa 2011 -

Strany 80

Year of Construction Year of Air-barrier retrofit? Number of Stories Floor Area Enclosure Area Tested Permeablity ft2 ft2 cfm/ft2 @75Pa 2012 -

Strany 81

Acceptable air leakage? For a 4 story building, 120 x 110 x 8 ft, n=0.65 CFM75/ ft2 USA ASHRAE 90.1 Leaky 0.60 USA Washington State 0

Strany 82 - Test Scenarios

Real life test: EMAD Antwerp, Belgium • Envelope Area = 11,250 m2 • 0.601 CFM/ft2 @ 75Pa • 8.22 m3/h/m2

Strany 83 - FanTestic software

Real life test: BTC South Carolina, USA • Envelope A = 136,820ft2 • 0.08 CFM/ft2 @ 75Pa • 1.5 m3/h/m2

Strany 84 - Problem 1

Real life test: Retrotec Vancouver, Canada • Envelope Area = 25,000 ft2 • 0.4 CFM/ft2 @ 75Pa • 7.3 m3/h/m2

Strany 85 - Solution

Face page and graphs for MFT

Strany 87

Estimating how many fans you need

Strany 88 - Problem 3A

 Press [Time Avg], until test pressure varies less than 1Pa.  Wait for 2X time average period before taking a reading. ◦ Stabilizes readings

Strany 89 - Problem 3B

Calculation based on a desired leakage requirement

Strany 90

Calculation using Retrotec’s ‘Number of Fan Calculator’ Spreadsheet

Strany 91 - Connections that work best

Test Scenarios (“Individual Control” with FanTestic) Developed by Retrotec Inc.

Strany 92

FanTestic software

Strany 93

One Zone: Testing a single-zone enclosure requiring multiple fans. Problem 1

Strany 94 - Exercises

One Zone: Testing a single-zone enclosure requiring multiple fans. Solution

Strany 95

Multiple Zones: Testing multiple zones requiring one fan on each separate zone. (These zones can be adjacent rooms or separated floors) Problem 2

Strany 96 - Red tubes attached

Solution Multiple Zones: Testing multiple zones requiring one fan on each separate zone. (These zones can be adjacent rooms or separated floors)

Strany 97

Multiple Zones: Testing multiple zones requiring multiple fans on each separate zone. (These zones can be adjacent rooms or separated floors) Problem

Strany 98

Multiple Zones: Testing multiple zones requiring multiple fans on each separate zone. (These zones can be adjacent rooms or separated floors) Problem

Strany 99

 Use [@ Pressure] key (if available)  Increase Time Average to minimize fluctuation ◦ Wait at least double the time averaging period before taking a

Strany 100 - Imbalanced test fan flow –

Multiple Zones: Testing multiple zones requiring multiple fans on each separate zone. (These zones can be adjacent rooms or separated floors) Solution

Strany 101 - Developed by Retrotec Inc

Connections that work best (Control cables) Developed by Retrotec Inc.

Strany 104

Large Building Testing Exercises Developed by Retrotec Inc.

Strany 105

Imbalanced test fan flow caused by individual set points Click to play video Developed by Retrotec Inc. Exercise 1

Strany 106

Control Cable Control Cable Imbalanced test fan flow caused by individual set points Exercise 1 Red tubes attached with T-connecters

Strany 107

Imbalanced test fan flow caused by individual set points 1. What is the difference between the two Door Fan speeds? (Pick the closest answer) 2%

Strany 108

Imbalanced test fan flow – Solution : common set point Click to play video Developed by Retrotec Inc. Exercise 2

Strany 109

Control Cable Imbalanced test fan flow caused by individual set points Exercise 2 Only 1 gauge controls the speed of both fans